6F2T0207 (0.01)GRE200 (5,6)- 965 -(v) Setting of MeasurandsIn Measurand frame of the IEC 60870-5-103 standard, numerical information such as powersystem quantities are responded for Class 2 cyclic request from upper system (station). TheIED can provide numerical information, which is converted the numerical information inmetering table according to user setting weight.When the “Measurands” item is selected on the start screen of the GR-TIEMS, thesetting screen is displayed.Figure 11.5-11 “Measurands” setting screenFigure 11.5-12 “Measurand1” setting screenIn one frame of Measurand, the Type ID, INF, FUN settings, and its position setting(Measurement Name/Measurement Description/Lower Limit/Upper Limit/Coefficient)must be set. “No.” shows the position of power system quantity. (For details, describe later.)The maximum 16 items of Measurands and the maximum 32 power system quantities perone frame can be set.Common address is linked with the address setting† of the relay.†For more information, seeAppendix: IEC 60870-5-103 interoperability (→page1118).