Toshiba GR-200-5 Instruction Manual
Also see for GR 200 Series: Instruction manualInstruction manualInstruction manualInstruction manualInstruction manual
6F2T0207 (0.01)GRE200 (5,6)- 548 -4.2.8 SettingDPOS01(Function ID: 512001) at Change Over SwitchSetting items Range Unit Contents Default NoteCommon DPOS-NELD 0 - 99 - Number of Event lock detect time 10DPOS-TELD 1 - 99 s Timer of detect event lock 10DPOS-TELR 1 - 99 s Timer of recovery from event lock 10DPOS01-EN Off / On - DPOS01 switch for Device01 OffDev01 DPOS01-DEVNAME [Preferred text] - item name of DPOS_Dev1 DPOS_Dev1 !DPOS01-00NAME [Preferred text] - state name of (0,0)state Travelling0 !DPOS01-01NAME [Preferred text] - state name of (0,1)state Off !DPOS01-10NAME [Preferred text] - state name of (1,0)state On !DPOS01-11NAME [Preferred text] - state name of (1,1)state Travelling1 !DPOS01-UDFNAME [Preferred text] - state name of undefined Undefine !DPOS01-FLTNAME [Preferred text] - state name of faulty Faulty !DPOS01-DEVTYPE 1-Pole / 3-Pole /switch - Device Type 1-PoleDPOS01A-NOPSG [Preferred signal] - Normally Open Signal of the single-pole orphase ANot assignedDPOS01A-NOPSGI Off / On - Signal inverse or not OffDPOS01A-NCLSG [Preferred signal] - Normally Close Signal of the single-pole orphase ANot assignedDPOS01A-NCLSGI Off / On - Signal inverse or not OffDPOS01B-NOPSG [Preferred signal] - Normally Open Signal of phase BNot assignedDPOS01B-NOPSGI Off / On - Signal inverse or not OffDPOS01B-NCLSG [Preferred signal] - Normally Close Signal of phase BNot assignedDPOS01B-NCLSGI Off / On - Signal inverse or not OffDPOS01C-NOPSG [Preferred signal] - Normally Open Signal of phase CNot assignedDPOS01C-NOPSGI Off / On - Signal inverse or not OffDPOS01C-NCLSG [Preferred signal] - Normally Close Signal of phase CNot assignedDPOS01C-NCLSGI Off / On - Signal inverse or not OffDPOS01-OPC And / Or - Normally Open contact grouping AndDPOS01-CLC And / Or - Normally Close contact grouping OrDPOS01-SPPEN Off / On - Automatic event suppression function OffDPOS01-UDFEN Off / On /CHKONLY - undefined pallet check function OffDPOS01-UDFTIM 0.1 - 100.0 s palette Undefined check timer 30.0DPOS01-FLTEN Off / On /CHKONLY - faulty pallet check function OffDPOS01-FLTTIM 0.1 - 100.0 s palette faulty check timer 30.0DPOS01-CTREN Off / On - control mode (control enable) OffDPOS01-CTRMENU Off / On - control by MENU enable OffDPOS01-CTRAHMI DIR / SBO - control action(Direct or SBO)by HMI SBODPOS01-NSLBORD1 [Preferred signal] - select binary output read data(DataID)1 for nodirection select command 5120018903011DC0DPOS01-NSLBORD2 [Preferred signal] - select binary output read data(DataID)1 for nodirection select command 5120018903011DC0DPOS01-FSLBORD [Preferred signal] - select binary output read data(DataID) for offdirection select command 5120018A03011DC4DPOS01-OSLBORD [Preferred signal] - select binary output read data(DataID) for ondirection select command 5120018603011DC6DPOS01-FEXBORD [Preferred signal] - execute binary output read data(DataID) foroff direction execute command Not assignedDPOS01-OEXBORD [Preferred signal] - execute binary output read data(DataID) foron direction execute command Not assigned |
Related manuals for Toshiba GR 200 Series
This manual is suitable for:
Product
Menu
Learn More
Menu
Legal
Menu
Copyright © 2024 OneStart. All Rights Reserved