6F2T0207 (0.01)GRE200 (5,6)- 1095 -(PIXIT Ed.1&Ed.2)14. PIXIT FOR CONTROL MODEL(Continued)ID Ed Description Value / ClarificationCt9 1,2Which additional cause diagnosis aresupportedY UnknownY Not-supportedY Blocked-by-switching-hierarchyY Select-failedY Invalid-positionY Position-reachedN Step-limitY Blocked-by-ModeN Blocked-by-processY Blocked-by-interlockingY Blocked-by-synchrocheckY Command-already-in-executionY Blocked-by-healthY 1-of-n-controlY Abortion-by-cancelY Time-limit-overY Abortion-by-trip (only for BCPU)Y Object-not-selectedEdition 1 specific values:Y Parameter-change-in-executionEdition 2 specific values:Y Object-already-selectedN No-access-authorityN Ended-with-overshootN Abortion-due-to-deviationN Abortion-by-communication-lossN Blocked-by-commandN NoneY Inconsistent-parametersY Locked-by-other-clientN Parameter-change-in-execution*Ct10 1,2 How to force a “test-not-ok” respond withSelectWithValue requestSet orCat with unsupported value.See below “Which origin categoriesare supported?”Ct11 1,2 How to force a “test-not-ok” respond withSelect requestSend SELECT request to the controlobject which is not mapped tocontrol application.