6F2T0207 (0.01)GRE200 (5,6)- 516 -4.2-13 for PLC#1, Table 4.2-14 for PLC#2, Table 4.2-17 and Table 4.2-19 for outputsignals.‡‡Note: The “Operate failed” signal is issued when the state-change is not detected untilafter reaching the time set by the [DPOS01-RST].(iv) Receiving “Operate command Off” from the local-endFigure 4.2-25 outlines the reception of the operate command ‘Off ’ from the local-end.Signal reception fromthe front panelOperate command Off from the local-endDo nothingOperatedecisionSuccessFailedOperate logicWait for a commandSignal outputOperate command On from the local-endOperate command Off from remote-endOperate command On by the PLC functionOperate command Off by the PLC functionWait for a next commandSelect stageSelect command Off from the remote-endSelect command On from the remote-endSelect command Off from the local-endSelect command On from the local-endSelect command On by the PLC functionSelect command Off by the PLC functionOperate command On from remote-endFigure 4.2-25 Outline of Operate command ‘Off’Input signal generated at the local-endFigure 4.2-26 illustrates the operate logic when an “Operate command Off (Local-OFF-Control)”signal is applied to the DPOS01 logic. The input signal is provided when “Execution for Off” iskeyed on the IED front panel.Output signal to BOThe DPOS01 function, in Figure 4.2-26, can issue an “Operate” signal at the output point“DPOS01_FEX_BO”, when the DPOS01 function determines that the input signal “Local-Off-Control” is true.