6F2T0207 (0.01)GRE200 (5,6)- 528 -(i) Receiving “change value for counter” from the remote-endMapping of Input signal requiredFigure 4.2-34 depicts the logic when a command “change value for counter” is received at theDPOS01 logic. With regard to a three-phase counter, the input-point“DEV01_3PH_CONTROL_REQ” is used. With regard to a phase-A counter, the input-point“DEV01_APH_CONTROL_REQ” is used. For phase-B and phase-C, the input-points“DEV01_BPH_CONTROL_REQ” and “DEV01_CPH_CONTROL_REQ” are used.DPOS01 function (Function ID: 512001)Operate CommandDEV01_3PH_REQCommand “change value for counter”512001_7003016D09&“DPOS01_SLD_CSCN”(512001 8A03031F86)Input OutputOperate logic in DPOS01Operate condition‡Figure 4.2-34 Changing counter value for three-phase† with operation from the remote-end inDPOS01‡Note:The “operate condition” signal is provided from the operate condition logic ofFigure 4.2-36.†Note: The user can apply other counter change commands for phase-A, -B, and –C asshown in Table 4.2-22. The resultant signals for the other DPOS02-72 logics areshown in Table 4.2-23.Output signal to BOThe DPOS01 function can issue a “Result” signal at output point “DPOS01_SLD_CSCN”.(ii) Receiving “change value for counter” from the local-endInput signal from the front panelFigure 4.2-35 depicts the logic when a “change value for counter” command is provided in theDPOS01 function. The command is provided from the sub-menu, as shown in Figure 4.2-33.DPOS01 function (Function ID: 512001) “DPOS01_SLD_CSCN”(512001 8A03031F86)Input OutputOperate logic in DPOS01Command “Change value”Figure 4.2-35 Changing counter value by operation from the front panel in DPOS01Output signal to BOThe DPOS01 function can issue a “Result” signal at output point “DPOS01_SLD_CSCN”.