6F2T0207 (0.01)GRE200 (5,6)- 383 -GCNT01 function (Function ID: 54001)“GCNT01_SLD_CSCN”(540001 8A0E011E76)GCNT01_CMM_REQCommand “Remote-Reset-Control”Either “SBO mode” or “DIR mode”(e.g., “ctlmodel” in IEC61850*) In SBO operateIn DIR operateSelect “Failed”540001 700E016D09To BO connectionInput OutputSelect logic in GCNT010.2s0 t0.3s0 t&&&CompleteSelect condition‡1≥Select commandOperate commandFor SBO operationFor DIR operationTo “Wait for a command”To “Wait for a nextcommand”“GCNT01_SLF_CSCN”(540001 8B0E011E7B)Figure 3.5-6 Select ‘Reset’ in GCNT01††‡Note:A “select condition” signal is provided from the select condition logic. For moreinformation, see Figure 3.5-7.*Note:The GNCT01 function can run in either the “SBO mode” or the “DIR mode” usinga signal called “ctlmodel” when communication is implemented using IEC61850.To use this signal, the user should map it for IEC61850 communication.††Note: To identify the input and output points of the other GCNT02–GCNT32 logics, seeTable 3.5-1 for the inputs and Table 3.5-4 for the outputs.