6F2T0207 (0.01)GRE200 (5,6)- 801 -(iii) Fail output and BO circuit driveAutomatic supervision function can drive Fail contact (N/C or “b” contact) on BIO module atT1† when an error occurs without warning. Note that, the drives for respective BO circuits‡on BIO will be locked out when serious error (Level 1=Critical error) is detected.Table 10.1-4 FAIL contact, BO, LED outputs depending on levelsErrorLevelsFAIL† contact outputs BO‡ locked out ErrorLEDScrew No. 19 (N/C)0: No error Open Not locked out Off1:Serious Closed Locked out On2:Serious(Comm.) Open Not locked out On3:Minor Open Not locked out On4:Alarm Open Not locked out Off5:Warning Open Not locked out OffError outputted with FAIL contact†If serious error (Level1) is detected by Automatic supervision function, N/C contact will turnto be closed. Table 10.1-4 shows N/O contact is open, except serious error.Locking out of BO circuit drive‡BO operation will be locked out, when serious error (Level1) is detected. Note that it will stopissuing trip commands on BO circuits. If the error is cleared, the operations will be back.†Note:See ChapterTechnical description: DC power and Fail terminals. (→p. 672).‡Note:BO is discussed in ChapterTechnical description: Binary output circuit (→p. 650).(iv) Affection of application operation by error levelsThe error levels influence the operation of relay and control and monitoring application.Table 10.1-5 Operation states in the IED applications affected by the error levelsLevels Relay applications Control and monitoring applications Notes0: No error – –1: Serious Stopped Stopped2: Serious (Comm.) Not affected† Not affected3: Minor Not affected Stopped4: Alarm Not affected Not affected5: Warning Not affected Not affected†Note: Serious (Comm.) can be related to communication of tele-protection applications.