6F2T0207 (0.01)GRE200 (5,6)- 540 -Setting for the contact health check (normal setting, example #1)Figure 4.2-49 shows a setting example for the 43SW scheme. Select and operate commandsdrive the BO1 to BO4 contacts. To check that the contact health check function is workingcorrectly, the respective points of the BO-RBs should be connected as shown in Table 4.2-28, todemonstrate that the settings are physically matched with the BO contacts.Table 4.2-28 Setting example for contact health checkExample #1 Contact health check settings for example #1“DPOS01_OSL_BO_FLG” is connected to “BO1” at IO#1-2 200B41 8002001113(BO1-RB) set for [DPOS01-OSLORD] OK“DPOS01_FSL_BO_FLG” is connected to “BO2” at IO#1-2 200B41 8102011113 (BO2-RB) set for [DPOS01-FSLBORD] OK“DPOS01_OEX_BO_CSF” is connected to “BO3” at IO#1-2 200B41 8202021113(BO3-RB) set for [DPOS01-OEXBORD] OK“DPOS01_FEX_BO_CSF” is connected to “BO4” atIO#1-2 200B41 8302031113(BO4-RB) set for [DPOS01-FEXBORD] OKPlus (+)“DPOS01_OSL_BO_FLG”(512001 8603011DC6) SW1 driven withBO1 at IO#1-2BO1DriversSelect command On“BO1-RB”(200B41_8002001113)BO3“DPOS01_OEX_BO”(512001 8203011DD3)“BO4-RB”(200B41_8302031113)BO4“DPOS01_FEX_BO”(512001 8103011DD0)“BO3-RB”(200B41_8202021113)SW2 driven withBO2 at IO#1-2SW4 driven withBO4 at IO#1-2Remote/Local-endSW 3SW 1Minus (−)BIO module43SWOncommandBO2“DPOS01_FSL_BO_FLG”(512001 8A03011DC4)“BO2-RB”(200B41_8102011113)SW 2SW 4SW3 driven withBO3 at IO#1-2Select command OffOperate command OnOperate command OffOffcommandFigure 4.2-49 Contact health check setting and 43SW scheme for example #1