6F2T0207 (0.01)GRE200 (5,6)- 895 -Edit GOOSE Control BlockGOOSE control block is used to exchange information between IEDs. GOOSEmessages are used for interlock operation between IEDs in order to protect theelectrical system. GGIO1 is used for sending high-speed GOOSE messages. TheDataID assigned to GGIO1 is sent within 3ms.If the user wishes to assign the DataID for GOOSE operation, follow the stepsbelow:1. Click GGIO1 and select Ind1 as shown in Figure 11.3-19.2. Drag and Drop the required signals to be sent by GOOSE.Note: The user can assign any signal to GGIO1->Ind1~16 for high-speed GOOSE, asrequired.DropDragFigure 11.3-19 Signal mapping for high speed GOOSEAs shown in the above figure, signals are assigned to “System/GGIO1$Ind1”. Theuser can assign signals to other GGIOs (for example, GGIO2, GGIO3 and so on)which are not meant for high-speed GOOSE operation.