6F2T0207 (0.01)GRE200 (5,6)- 834 -10.2.32 Supervision of communication setting (Commslv error)A setting error can be detected if contradictory data has been set in the memory. Errormessages are shown depending on a kind of the communication protocols.(i) Error levelThe default error level has set at level 3 (Minor error), but the user can change it using setting[CHK_CMLV:LVl]; and then, set On for the setting [CHK_CMLV:Sw]. Errors can be detected intwo minutes after the IED switches on.(ii) Error messageWhen detecting errors, an error message can be shown on the LCD screen and an LED turnson.Table 10.2-63 Error messages provided by the supervisor in CHK_CMLVMessage and level Meaning of the informationData(cmmslv) error Detection of the failure in the settingsError level Minor error (Level 3)(iii) Setting error informationIf a signal mapping has not been performed correctly, error messages be shown in Hexadecimalcodes.Table 10.2-64 61850 setting error information in CHK_CMLVDisplayareaMeaning of the detailed informationLeft column Right columnTop row0001xxxx: IEC61850 error0008xxxx: Modbus error0010xxxx: IEC60870-5-103 errorNumber (high-order) of Data IDmistakenly be mapped in the IEDMiddle row Number (low-order) of Data IDmistakenly be mapped in the IED Internal informationBottomrow Internal information Internal informationFigure 10.2-1 Sample error messageNote: Figure 10.2-1 is an example of 61850 error; and the content of that can bedifferent depends on degree errors; hence, this is just an example:• The first of the top left part (i.e., “0001”) is showing the error belongs tothe IEC61850 protocol.Data(cmmslv) error10:48 1/1[Minor error][00010004] [51200131][03011001] [4747494F][32245354] [7456616C]