6F2T0207 (0.01)GRE200 (5,6)- 428 -Output signal to BOThe DPSY01 function, in Figure 4.1-4, can issue a “Select success” signal at the output point“DPSY01_FSL_BO_FLG” when the DPSY01 function determines that the “Selection commandOpen (Remote-Open-Control)” signal is true. If the DPSY01 function determines that the“Remote-Open-Control” signal is not true, the DPSY01 function returns to the “Wait for acommand” stage.(iii) Receiving “Select command Closing” from the local-endFigure 4.1-5 outlines the reception of the select command ‘Closing’ from the local-end.Signal receptionfrom the front panelSelect command Closing from the local-endSignal outputSelectdecision SuccessFailedSelect logicSelect stageCancel logicWait for a next commandCancel commandWait for a commandOperate logicOperate commandCancel logicOperate logicSelect command Open from the remote-endSelect command Open from the local-endSelect command Closing by the PLC functionSelect command Open by the PLC functionSelect command Closing from the remote-endFigure 4.1-5 Outline of select command for ‘Closing’Input signal generated at the local-endFigure 4.1-6 shows the select logic when a “Select command Closing (Local-Closing-Control)”signal is applied to the DPSY01 function. The signal is provided when a “Selection for Closing”key is pressed on the IED front panel; the user is not required to map the signal from theIEC61850 communication. Note that the user should set the scheme switch [DPSY01-CTRAHMI] to SBO when operation from the IED front panel is required.