6F2T0207 (0.01)GRE200 (5,6)- 761 -Transferred information during faultThe IED can transfer the information for the fault duration in the IEC61850 communication†.†Note:The transferring is only available in “Edition1 with option” or “Editon2” of theIEC61850. For the information about the option, see ChapterCommunicationprotocol: IEC 61850 communication: About protocol, separately (→p. 877).8.4.1 Transferred metering valuesTable 8.4-1 shows transferring information during the fault†. When the IED is running on theIEC61850 Edition1 option, these signals should be mapped for Private Object AnInDatUpd.When the IED is running on the IEC61850 Editon2, they should be mapped for Normal ObjectAnIn.Table 8.4-1 Transferred values taken during the faultItems Signalsnames Unit Model GRE200-§5 6Ia (Primary) FLTMS0001 A ✓ ✓Ib (Primary) FLTMS0004 A ✓ ✓Ic (Primary) FLTMS0007 A ✓ ✓Ie (Primary) FLTMS0010 A ✓ NAIse (Primary) FLTMS0013 A NA ✓I1 (Primary) FLTMS0016 A ✓ ✓I2 (Primary) FLTMS0019 A ✓ ✓I0 (Primary) FLTMS0022 A ✓ ✓Vab (Primary) FLTMS0025 V ✓ ✓Vbc (Primary) FLTMS0028 V ✓ ✓Vca (Primary) FLTMS0031 V ✓ ✓Va (Primary) FLTMS0034 V ✓ ✓Vb (Primary) FLTMS0037 V ✓ ✓Vc (Primary) FLTMS0040 V ✓ ✓Ve (Primary) FLTMS0043 V ✓ ✓Vs (Primary) FLTMS0046 V ✓ ✓I2/I1 FLTMS0049 – ✓ ✓THM-Capacity FLTMS0052 % ✓ ✓Note: See section 8.1.1(vi) about the information about fault recording quantities. Tofind Data ID, see section 8.4.4.§Note:Model is chosen by the number of at ordering codes at positions T. See Softwareselection inAppendix: Ordering (→p. 1133).