6F2T0207 (0.01)GRE200 (5,6)- 391 -(iii) Select conditionSimilar to the select condition (see Chap.3.5.2(ii)), the GCNT01 function has an operate-condition logic. Figure 3.5-14 shows the operate-condition logic.Operate conditionGCNT01 function (Function ID: 540001)To operate logicFrom Control hierarchy *5From CMNCTRL[GCNT01-HMI]OnOther devices traveling detected*3Traveling ORGCNT00IN_TMP_51540001 800E00ED5ASERI_ERR&&1≥Unmatched condition detected *4Serious error detection[DPOS01-EN]OnFigure 3.5-14 Operate condition logic for GCNT011–5Note: The signals and settings in Figure 3.5-14 are same as the signals shown inFigure 3.5-7.(iv) Signal names and numberTable 3.5-8 PLC monitoring points (Output signal for BIO)Signal Number Signal Name Description540001 820E011E84 GCNT01_EC_OK_CSCN GCNT01 execute command OK condition signal540001 820E021E84 GCNT02_EC_OK_CSCN GCNT02 execute command OK condition signal540001 820E031E84 GCNT03_EC_OK_CSCN GCNT03 execute command OK condition signal…. …. ….540001 820E201E84 GCNT32_EC_OK_CSCN GCNT32 execute command OK condition signal