6F2T0207 (0.01)GRE200 (5,6)- 633 -(i) CTs for three phase currentsDepending on actual CTs arrangements, the user can select a style among No. 101–104. Finda matching style and define it by settings [Conn-CT] and [2P_Type].Table 5.4-2 Connection styles for CTs for three phase currentsNo. Connection styles Combination settings Wiring examples[Conn-CT] [2P_Type]101 Not to input No use (N/A)No current inputted to CT-IL1, IL2 and IL3IL112IL234IL356BusbarA B C------102To input3-phase currentsfrom 3-phase CTs3P (N/A)3-phase currents (Ia, Ib and Ic) inputted toCT-IL1, IL2 and IL3IL112IL234IL356BusbarA B CIaIbIc103To input2-phase currentsfrom 2-phase CTs2P12-phase currents (Ia and Ic) inputted to CT-IL1 and IL3IL112IL234IL356BusbarA B CIa--Ic104To input3-phase currentsfrom 2-phase CTs23-phase currents (Ia, Ib and Ic) inputted toCT-IL1, IL2 and IL3IL112IL234IL356BusbarA B CIaIbIc