6F2T0207 (0.01)GRE200 (5,6)- 411 -3.7.4 Signal for Local/Remote controlNote: The meaning of the following references are used in the column “M/O” in TablesTable 3.7-2, Table 3.7-3, and Table 3.7-4:“O” means the signal is optional.“M” means the user should map/set/configure the signal; otherwise, the usermay experience an operational failure if the default settings are used.“N/A” means that the user cannot change the state of the signal.Table 3.7-2 PLC connection point (Input point for LOCRMT)Signal Number Signal Name Description M/O240001 31000A1735 L/R CHG [L/R] key “push” N/A530001 800901EDE0 LRSW01_PLC_SGN01 Disable condition by PLC O530001 800901EDE1 LRSW01_PLC_SGN02 User configurable condition by PLC OTable 3.7-3 Mapping points for LOCRMTSignal Number Signal Name Description M/O530001 3009011008 LRSW01_LR_ORCAT Mapping data for “originator” in IEC61850 N/A530001 6A09011009 LRSW01_LR_ORIDENT Mapping data for “originator” in IEC61850 N/ATable 3.7-4 PLC monitoring point (LOCRMT)Signal Number Signal Name Description530001 3109001001 LRSW01_LR_ST Local(T) / Remote(F) status (single bit expression)530001 3009011001 LRSW01_LR_ST_RMT Local(0x40) / Remote(0x80) status (double bit expression)