6F2T0207 (0.01)GRE200 (5,6)- 441 -Output signal to BOThe DPSY01 function, illustrated in Figure 4.1-17, is able to issue a “Select to cancel” signalat the monitoring point “DPSY01_CC_SS”, when the DPSY01 function determines that the“Local-Cancel” signal is true.(iii) Cancel condition logicFigure 4.1-18 shows the cancel condition logic. As the criteria “Unmatched condition detected”is connected normally for the cancel logic, set Fixlogic for the scheme switch [DPSY01-LGCNFFCT].DPSY01 function (Function ID: 511001)User configurable condition (PLC connection point) Fixedlogic[DPSY01-LGSLFFCT]To cancel logic inDPSY01Unmatched conditions detected *1DPSY01IN_TMP_46511001 800201EE69&&1≥PLC#1Figure 4.1-18 Logic “Cancel condition” in DPSY011Note: The criteria “unmatched conditions” are determined when the “Test-bit status” inthe ‘cancel’ command is not identical to the “IED test status”.2Note: With the exception of the above ‘cancel’ logic, there is an operate-condition logicwithin the DPSY01 function; the operate-condition logic will always checksconditions. That is, the user is only required to set either the “operate-condition”or the “cancel-condition” logic.If the original logic does not meet with the requirements of the user, it can be replacedusing the connection point “User configurable condition”:1. Connect the user-customized logic with the “DPSY01IN_TMP_46”, which is listed in Table 4.1-11.2. Set scheme switch [DPSY01-LGCNFFCT] to PLC.(iv) Signal name and numberNote: The user should note the following descriptions shown in the column “M/O” ineach table:“O” indicates that the signal is provided for optional usage.“M” indicates that the user should map/set/configure using the signal;otherwise, the user may experience an operational failure for the defaultsettings.“N/A” indicates that the user cannot change the state of the signal.