6F2T0207 (0.01)GRE200 (5,6)- 1019 -The following shows how to operate in this screen.TimeSyncSrc menuTime SyncSrc (Time Synchronization Source) can be changed by the following procedure.1) Move cursor to the TimeSyncSrc menu and press ENTER.2) The TimeSyncSrc menu is composed of “---”, SNTP, BI,MODBUS and IRIG-B.Note: When “---” is selected, it means that time synchronization isnot operated.By using time synchronization via Ethernet with a SNTP server, the user can connect up to amaximum of four SNTP servers. If more than one SNTP is used, the priority of the servers canbe decided in ascending order of synchronized stratum value (in order of higher-accuracy) andselect the server with the smallest value.SNTP settingIP address of SNTP server can be set by the following procedure.1) Confirm that the SNTP synchronization function is set for On.Subsequently move cursor to the SNTP menu and press ►.2) Move cursor to desired server number and press ENTER.SNTP10:48 1/4_Server1 +0. 0. 0. 0Server2 +0. 0. 0. 0Server3 +0. 0. 0. 0TimeSyncSrc10:48 1/5---_SNTPBIMODBUSIRIG-BTime Sync10:48 1/4_TimeSyncSrc +SNTPSNTP +>OnBI SYNC +>OffMODBUS SYNC +OffIRIG SYNC +>OffTime Sync10:48 1/4TimeSyncSrc +SNTP_SNTP +>OnBI SYNC +>Off