6F2T0207 (0.01)GRE200 (5,6)- 442 -Table 4.1-11 PLC connection points (Input signal for ‘cancel’ condition)Signal Number Signal Name Description M/O511001 800201EE69 DPSY01IN_TMP_46 DPSY01 user configurable cancel condition O511001 800202EE69 DPSY02IN_TMP_46 DPSY02 user configurable cancel condition OTable 4.1-12 PLC monitoring points (Output signal for ‘cancel’ condition)Signal Number Signal Name Description511001 8602011E95 DPSY01_CC_SS DPSY01 cancel succeed511001 8602021E95 DPSY02_CC_SS DPSY02 cancel succeed511001 8702011E96 DPSY01_CC_FS DPSY01 cancel failed511001 8702021E96 DPSY02_CC_FS DPSY02 cancel failed(v) Setting nameNote: The “xx” within “DPSYxx” represents the DPSY function number. (e.g., if DPSY01is considered, the “xx” is equal to “01”. The numbers used for “xx” can berepresented by either “01” or “02”.)Table 4.1-13 Setting for ‘Cancel’ in DPSYxxSetting Name Description Default Setting item or valueDPSYxx-LGCNFFCT Logic selector for cancel condition (DPSY01-02) Fixedlogic Fixedlogic / PLC