6F2T0207 (0.01)GRE200 (5,6)- 1048 -SettingSetting of Test flagSetting item Range Units Contents Defaultsetting value NotesTestFlag-EN Off / On - Change test flag on Protocol OnS-TestFlagCancel Off / On - Test flag of slave communication protocol is canceled OffGOSNDBLK Off / On - GOOSE publishing block OffGOSUBBLK Off / On - GOOSE subscription block OffSetting of Test optionSetting item Range Units Contents Defaultsetting value NotesA.M.F. Off / On - Supervisor function use or not OnCLP-Test Off / STATE0 / STATE3 - Forcibly changing to CLP state OffTHM-Test Off / On - Test opinion for the setting[THM-IP] OffTHM-IP 0.00 - 5.00 - Previous load current for thermal testing 0.00SOTF-Test Off / On - Forcibly establishing the cold load condition OffUV-Test Off / On - Not to execute UV block function OffUVS-Test Off / On - Not to execute UVS block function OffSHOTNUM-Test Off / S1 / S2 / S3 / S4 / S5 / S6 - Auto reclose test shot number OffMot-Status Off / Stop / Start-up / Running - Forcibly change the motor status OffMot-THM-Test Off / On - Test option for the setting [Mot-THM-IP] OffMot-THM-IP 0.00 – 5.00 A Previous load current for thermal testing 0.00Mot-STPH-Reset Off / On - Reset for Motor starts per hour function OffFSCxx-SET Normal / Off / On - Forcibly control style for FSCxx signal NormalSYNC01-Test Off / On SYNC DEV1 synchronism check test mode OffSYNC02-Test Off / On SYNC DEV2 synchronism check test mode Off