6F2T0207 (0.01)GRE200 (5,6)- 759 -8.3.7 SettingDISTURB_REC(Function ID: 200401)Setting items Range Unit Contents Default NoteRecord Time 0.1 - 10.0 s Time for disturbance recording 3.0Pre-fault Time 0.1 - 10.0 s Pre-fault time 0.3Trip Trig.SW Off / On – Operation with the TRC trip command OnDISTURB_REC(Function ID: 200401)Setting items Range Unit Contents Default NoteBinary Signal1 (Preferred DataID) – Logic signal1 for the operationSee Setting tablein this sectionBinary Sig.Name1 (Preferred name) – Name of the logic signal1Binary Signal2 (Preferred DataID) – Logic signal2 for the operationBinary Sig.Name2 (Preferred name) – Name of the logic signal2Binary Signal3 (Preferred DataID) – Logic signal3 for the operationBinary Sig.Name3 (Preferred name) – Name of the logic signal3…… …… – ………… …… – ……Binary Signal256 (Preferred DataID) – Mode setting for the detectionBinary Sig.Name256 (Preferred name) – Name of the trigger signal768DRT_MV(Function ID: 4B0081)Setting items Range Unit Contents Default NoteOC-DRT-EN Off / On – Disturbance Record Trigger OC-DRT enable OffOC-DRT 0.10 - 150.00 A OC-DRT relay operating value 1.00EF-DRT-EN Off / On – Disturbance Record Trigger EF-DRT enable OffEF-DRT 0.10 - 150.00 A EF-DRT relay operating value 0.20UV-DRT-EN Off / On – Disturbance Record Trigger UV-DRT enable OffUV-DRT 5.0 - 130.0 – UV-DRT relay operating value 0.20UVS-DRT-EN Off / On – Disturbance Record Trigger UVS-DRT enable OffUVS-DRT 5.0 - 130.0 V UVS-DRT relay operating value 51.0