6F2T0207 (0.01)GRE200 (5,6)- 150 -Setting of UV_MV (Function ID: 470181)Setting device Range Unit Contents Default NoteTUV4 0.00 - 300.00 s UV4 operating delay time (in DT mode) 1.00IDMT UV4 5.0 - 130.0 V UV4 threshold 60.0UV4-DPR 100 - 120 % UV4 drop-out/pick-up ratio 100UV4-TMS 0.010 - 100.000 - UV4 time multiplier (in IDMT mode) 1.000TUV4R 0.0 - 300.0 s UV4 definite time reset delay 0.0ORG UV4 5.0 - 130.0 V UV4 threshold 60.0UV4-DPR 100 - 120 % UV4 drop-out/pick-up ratio 100UV4-TMS 0.010 - 100.000 - UV4 time multiplier (in ORG mode) 1.000TUV4R 0.0 - 300.0 s UV4 definite time reset delay 0.0Output UV4-VTFBlk Non / Block - UV4 operation block by VTF NonUV4-UseFor Trip / Alarm - UV4 used for trip or alarm TripTest setting(Function ID: 470181)Setting device Range Unit Contents Default NoteTest option UV-Test Off / On - Not to execute UV block function Off