6F2T0207 (0.01)GRE200 (5,6)- 494 -(iv) Receiving “Select command Off” from the local-endFigure 4.2-7 outlines the reception of the Select command ‘Off ’ from the local-end.Signal receptionfrom the front panelSelect command Off from the local-endSignal outputSelectdecision SuccessFailedSelect logicSelect stageCancel logicWait for a next commandCancel commandWait for a commandOperate logicOperate commandCancel logicOperate logicSelect command On from the remote-endSelect command On from the local-endSelect command On by the PLC functionSelect command Off by the PLC functionSelect command Off from the remote-endFigure 4.2-7 Outline of Select command ‘Off’Input signal generated at the local-endFigure 4.2-8 shows the Select logic when a “Select command Off (Local-OFF-Control)” signalis received is applied to the DPOS01 function. The signal is provided when the user pressesthe “OFF” key on the IED front panel; the user is not required to map the signal from IEC61850communication.Output signal to BOWhen the “select condition” signal is true, the DPOS01 function can issue a “Select success”signal at the output-point “DPOS01_FSL_BO_FLG”.1Note: The signal “DPOS01_FSL_BO_FLG” is the same as the signal shown in Figure4.2-4. If the signal “Local-OFF-Control” is not true, the DPOS01 function returnsto the “Wait for a command” stage.