6F2T0207 (0.01)GRE200 (5,6)- 526 -Table 4.2-19 PLC monitoring points (Output signals for response)Signal Number Signal Name Description512001 8003011E93 DPOS01_EX_CMP DPOS01 completed control512001 8003021E93 DPOS02_EX_CMP DPOS02 completed control512001 8003031E93 DPOS03_EX_CMP DPOS03 completed control… … …512001 8003481E93 DPOS72_EX_CMP DPOS72 completed control512001 8603011E91 DPOS01_EX_FFL DPOS01 failed control512001 8603021E91 DPOS02_EX_FFL DPOS02 failed control512001 8603031E91 DPOS03_EX_FFL DPOS03 failed control…. …. ….512001 8603481E91 DPOS72_EX_FFL DPOS72 failed control(ix) Setting namesNote: The “xx” of “DPOSxx” represents the DPOS function number. (e.g., if the DPOS03is considered, the “xx” is equal to “03”. The suffix “xx” can be represented by “01”to “72”.)Table 4.2-20 Setting of Operate in DPOSxxSetting Name Description Default Setting item or valueDPOSxx-PLSM Methods of command output(DPOS1-72) Fix Fix/Var/LatchDPOSxx-CPW Duration of command output(DPOS1-72) 1.0[sec] 0.1~50.0[sec]DPOSxx-RST Detection time for terminating control (DPOS1-72) 30.0[sec] 0.1~100.0[sec]DPOSxx-LGCTRCON Logic selector for operate condition (DPOS01-72) Fixedlogic Fixedlogic/PLCDPOSxx-LGCFEXOT Logic selector for command output (DPOS01-72) Fixedlogic Fixedlogic/PLCDPOSxx-CTREN Activate control function of DPOS01-72 On Off / OnDPOSxx-LGEXFFCT Logic selector for operate condition (DPOS01-72) Fixedlogic Fixedlogic / PLC