6F2T0207 (0.01)GRE200 (5,6)- 898 -For example, to let a device execute “Select”, “Operate” and “Cancel” commandsfrom the sever through “CSWI4” and transmit the information to an IED, the usershould map an input point (Data ID) to several variables of “CSWI4” (See Figure11.3-22). Mapping period for Control shall be 100.*Note: For more information of the input points, see chapterGeneral control function orControl and monitoring application (→p. 487).Input DataIDDE V01_ CONTROL_ RE QSBOWOperCancelMappingFigure 11.3-22 Control function mappingTo complete the setting for control function, after mapping data, the user needsto set BI, BO† in the GR-TIEMS ->Setting.†Note:For more information for the BI, BO, see ChapterTechnical description: Binary IOmodule (→p. 650).