132Timing ChartOperation Timing after Power-ON• The above chart shows the timing from AC power-ON to command input.• Activate the external command input according to the above timing chart.Caution*1. In this term Servo-ON input (CN X5 SRV-ON:pin23) turns ON as a hard ware, but operation commandcan not be received.*2. Servo alarm output (CN X5 ALM:pin15) turns ON when the microcomputer's initialization is completed,and the condition of no error is occurring. Servo-ON input turns ON after Servo alarm turns ON and themain power supply is activated sufficiently.*3. After Internal control power supply , protective functions are active from approx. 1.5 sec after thestart of initializing microcomputer. Please set the signals, especially for protective function, forexample over-travel inhibit input (CWL,CCWL) or emergency stop input (EMG-STP), so as to de-cide their logic until this term.ONOFFPoint settingApprox. 100ms or more *1MIN 10msControl power supply(L1C,L2C)Internal control power supplyMicrocomputerMain power supply(L1, L2, L3)Servo alarm output(X5 Pin 15)Servo-ON input(X5 Pin 23)Dynamic brakeMotor energizedBRK-OFF output (X5 Pin 36)Point specifying input(P1IN - P32IN)Strobe signal(STB)OFFOFFONReset ONOFF ONOFF ONONOFFOFF (Brake engaged) ON(Brake released)OFFONNot energized EnergizedApprox. 10msor moreApprox. 10ms or moreApprox. 2sApprox. 1.5sApprox. 100 to 300msActivatedInitializeApprox.40msApprox. 2msApprox. 2ms0ms or more0s or more*2*3*2