2-24 BOP HIPWR 111315FIGURE 2-10. MASTER POWER UP SCREEN1. Adjust the limits to reflect the increased power capacity of the multiple unit combination asfollows:a. From the main screen, press % to enter the General Setup Menu.b. From the General Setup menu, Highlight Max/Min Settings and press !. Press @ torestore defaults. Verify that the Max/Min settings reflect the multiple unit combination. Forexample, for a parallel combination the values for +Current Max, –Current Min and ±Cur-rent Protect Max/Min now reflect the total current of the parallel combination. Voltage val-ues and limits reflect a series combination. For 2 X 2 and 3 X 2 combinations both currentand voltage are affected. NOTE: If desired, these limits may be lowered as described for astandalone unit (see PAR. 3.3.4).c. Press $ to save the settings upon power-up, then % to exit the General Setup menu andreturn to the power-up screenTABLE 2-13. SLAVE STATUS MESSAGE DEFINITIONSSlave Status MessageDisplayed on Master Power Up Screen(see Figure 2-10)MEANINGReady Unit is ready for operation.STANDBY If unit’s FAULT indicator is off, hardware error has NOT been detected,output is ready to be turned onNo Answer Unit is not responding to polls via BITBUS.Faulted Unit’s FAULT indicator is on to indicate a hardware error has beendetected.Not Used Unit is not part of parallel configurationUnknown Waiting for interface communicationMode Error Slave does not match voltage/current or parallel/series configurationexpected by master.VOLTAGESOURCECPROTECTVOLTAGE CURRENT