6F2S1931 (0.20)Centralized GRB200(Soft: 030, 031, 032, 033, 034)- 684 -see ChapterTechnical description: Binary IO module: Binary input circuit)The user can activate or turn off the above timers and switches using the setting function.To configure the binary input circuits, the user should follow the procedure in steps ((ii)-1 and(ii)-2)Selection of binary input circuit: For example, Figure 11.6-2 illustrates theselection of a binary input circuit on a binary IO module. Move the cursor bypressing keys ▲ and ▼. Then, press key ►to go to the next hierarchy.Figure 11.6-2 Selection of slot and binary input circuitNote: This screen is a sample. The slot numbers displayed depend upon theconfiguration of the binary IO module in each IED.CPL setting: Figure 11.6-3 is an example of a “Common” setting. From thisscreen, the user can set a threshold level and the number of comparisonsfeature for contact chatter for all binary input circuits.Figure 11.6-3 Common screenFor example, Figure 11.6-4 shows the CPL setting for binary input circuit (BI1).The timer and the inverse switch can be activated when On or Off is set for setting[BI1_CPL]. Press key ENTER to commence the setting of a switch or parameter.Binary Input10:48 2/32Slot#1 >_Slot#2 >Slot#3 >Slot#4 >Slot#5 >Slot#6 >[►]Slot#310:48 1/10_Common >BI1 >BI2 >BI3 >BI4 >BI5 >Common10:48 1/2Thres_Level +LowCmp_Num +4