6F2S1931 (0.20)Centralized GRB200(Soft: 030, 031, 032, 033, 034)- 480 -9.2.13 Supervision of sampling and transferring data (SA error)Sampling and transferring data with regard to the VCTs in MainUnit and SubUnit are checkedcyclically. The analog quantities computed in the CPU module of MainUnit are also checkedwith this function.(i) Error levelThe level of the error has been set at level 1 (Serious error1), as a default. However the usercan program the level using setting [CHK_SA:Lvl]. Set On for the setting [CHK_SA:Sw] tocheck the data transfer.(ii) Error messageWhen detecting an error, an error message can be shown on the LCD screen and an LED is lit.Table 9.2-26 Error messages provided by the supervisor in CHK_SA_CBPMessage and level Meaning of the informationSA#1 Error Data transfer error on the VCT#1 in MainUnitSA#2 Error Data transfer error on the VCT#2 in MainUnitSUB1 SA#1 Error Data transfer error on the VCT#1 in SubUnit#1SUB1 SA#2 Error Data transfer error on the VCT#2 in SubUnit#1SUB2 SA#1 Error Data transfer error on the VCT#1 in SubUnit#2SUB2 SA#2 Error Data transfer error on the VCT#2 in SubUnit#2Error level Serious error (Level 1)Table 9.2-27 Detailed information in Hexadecimal in CHK_SA_CBPDisplayareaMeaning of the detailed informationLeft column Right columnToprow00000001: SDRAM SA error00000002: ADC SA error00000004: FIFO full00000008: Waiting alarm00000010: Parity errorXXXX YYYYXXXX: SDRAM SA error numberYYYY: Expecting SDRAM SA numberMiddlerowXX YY ZZZZXX: Error SA valueYY: Expecting ADC SA No.ZZZZ: ADC SA error00000001: MAIN ADC#1Bottomrow 00000001: MAIN ADC#2 00000001: SUB1 ADC#1