6F2S1931 (0.20)Centralized GRB200(Soft: 030, 031, 032, 033, 034)- 549 -should check whether the required signals are mapped in the defaultconfiguration.*Note: There is no default configuration for GOOSE subscription. If GOOSE subscribefunction is required, then a new configuration has to be done.To verify the signals configured for the IEC 61850 protocol, the user should checkthe mapped data, Dataset or Report Control list. If they have existed, the signalsin the signal list should be matched with the attributes of LNs.Figure 10.3-11 shows an example to check if the signals are mapped in defaultconfiguration. For example, to check for mapping of the primary element signalin earth fault protection (EF1), follow the steps below:1. To check if the EF1 signal is already mapped in the LN, key ‘EF1’ under SignalName in the Signal List screen.“EF1” in signal listMapped dataFigure 10.3-11 Signal mappingAs shown in the above figure, the “EF1” signal is already mapped to LNattribute Prot/EF_PTOC1$Str1, general.2. To check if “Prot/EF_PTOC1$Str1, general” is already added in Dataset. Rightclick on “LLN0” and select Edit DataSet, then DataSet List screen appears asshown in Figure 10.3-12.