6F2S1931 (0.20)Centralized GRB200(Soft: 030, 031, 032, 033, 034)- 604 -193 not used208 not used209 not used224 not used225 not used240 not used241 not used254 Generic function type255 Global function typeDPI/Off, DPI/OnDouble-point information (DPI) is set using the menu as follows:DPI/Off: The frame is transmitted when the DPI/Sig.No. signal is OFF.DPI/On: The frame is transmitted when the DPI/Sig.No. signal is ON.Note: If selecting “-”(=don’t care), the frame is not transmitted even though theDPI/Sig.No. signal set change to the set status. In general, the frames relatedto tripping such as “Time-tagged message” and Time-tagged measurand”, etc.,which are not an object of GI (General Interrogation), are not transmittedwhen the DPI changes “On” to “Off”. In this case, set the “DPI/Off” to “-”(=don’tcare).Note: When selecting “DP” for both “DPI/Off” and “DPI/On”, the DPI number istransmitted as the number (=0/1/2/3) using the same information number(INF). Regarding the frame related to a device control, the “undefined/failed”status may be required in addition to the “close/open” status for the extension.When selecting “DP”, “undefined(00)/close(01)/open(10)/failed(11)” status isapplied in the same information number (INF).COTCause of Transmission (COT) of the frame is set. Not only one COT but also two or moreCOT can be selected each No. (frame). COT setting pattern and COT supplemented theframe are as follows:(1) If two or all of COT=1, 11 and 12 are checked per No., each frame of the No. becomethe following conditions.Table 10.4-7 COTCOT ConditionsCOT=12(remote operation) TR[ms] after receiving any command of the IEC 60870-5-1031COT=11(local operation) TL[ms] after Key operation on the relay front panel1COT=1(spontaneous)Conditions except above COT=11 and 12The relay is in test mode2, the COT=1(Spontaneous) is shifted to 7(Test mode)1Note: TR and TL are set in Common setting.2Note: Settings of the test mode is described later.(2) If one of COT is specified per No., the frame is always supplemented with the