6F2S1931 (0.20)Centralized GRB200(Soft: 030, 031, 032, 033, 034)- 148 -Setting (CH3) of CBP_OC(Function ID: 458B01)Setting item RangeUnits ContentsDefaultsettingvalueNotesCH3OC1OC1-EN Off / On – Enabling switch for OC1 element in CH3 OffOC1-TimerIEC-NI / IEC-VI / IEC-EIIEEE-MI /IEEE-VI /IEEE-EIUK-LTI/ US-CO2/ US-CO8DT/ Original- Delay type DTOC1 (in DT) 0.02 - 50.00 - Threshold in DT mode (multiple of CT 2nd rating) 1.00OC1 (in IDMT) 0.02 - 5.00 - Threshold in IDMT mode (multiple of CT 2nd rating) 1.00OC1-DPR 10 - 100 % Drop-out/Pick-up ratio 100TOC1 0.00 - 300.00 s Operating delay time (in DT mode) 1.00OC1-TMS-IEC 0.010 - 50.000 - Time multiplier in IEC inverse curve 1.000OC1-TMS-UK 0.010 - 50.000 - Time multiplier in UK inverse curve 1.000OC1-TMS-IEEE 0.010 - 50.000 - Time multiplier in IEEE inverse curve 1.000OC1-TMS-US 0.010 - 50.000 - Time multiplier in US inverse curve 1.000OC1-TMS-ORG 0.010 - 50.000 - Time multiplier in Original inverse curve 1.000OC1-Rtimer DEF / DEP - Reset delay type DEFTOC1R 0.00 - 300.00 s Definite time reset delay 0.00OC1-RTMS-IEEE 0.010 - 50.000 - Dependent reset time multiplier in IEEE inversecurve 1.000OC1-RTMS-US 0.010 - 50.000 - Dependent reset time multiplier in US inverse curve 1.000OC1-RTMS-ORG 0.010 - 50.000 - Dependent reset time multiplier in Original inversecurve 1.000OC1-k 0.00000 - 500.00000 - User original curve coefficient 0.00000OC1-a 0.00000 - 10.00000 - User original curve coefficient 0.00000OC1-c 0.00000 - 10.00000 - User original curve coefficient 0.00000OC1-kr 0.00000 - 500.00000 - User original curve coefficient 0.00000OC1-b 0.00000 - 10.00000 - User original curve coefficient 0.00000OC1-UseFor Trip / Alarm - OC1 out. selected for either Trip or alarm TripOC2OC2-EN Off / On – Enabling switch for OC2 element in CH3 OffOC2-TimerIEC-NI / IEC-VI / IEC-EIIEEE-MI /IEEE-VI /IEEE-EIUK-LTI/ US-CO2/ US-CO8DT/ Original- Delay type DTOC2 (in DT) 0.02 - 50.00 - Threshold in DT mode (multiple of CT 2nd rating) 1.00OC2 (in IDMT) 0.02 - 5.00 - Threshold in IDMT mode (multiple of CT 2nd rating) 1.00OC2-DPR 10 - 100 % Drop-out/Pick-up ratio 100TOC2 0.00 - 300.00 s Operating delay time (in DT mode) 1.00OC2-TMS-IEC 0.010 - 50.000 - Time multiplier in IEC inverse curve 1.000OC2-TMS-UK 0.010 - 50.000 - Time multiplier in UK inverse curve 1.000OC2-TMS-IEEE 0.010 - 50.000 - Time multiplier in IEEE inverse curve 1.000OC2-TMS-US 0.010 - 50.000 - Time multiplier in US inverse curve 1.000OC2-TMS-ORG 0.010 - 50.000 - Time multiplier in Original inverse curve 1.000OC2-Rtimer DEF / DEP - Reset delay type DEFTOC2R 0.00 - 300.00 s Definite time reset delay 0.00OC2-RTMS-IEEE 0.010 - 50.000 - Dependent reset time multiplier in IEEE inversecurve 1.000OC2-RTMS-US 0.010 - 50.000 - Dependent reset time multiplier in US inverse curve 1.000OC2-RTMS-ORG 0.010 - 50.000 - Dependent reset time multiplier in Original inversecurve 1.000OC2-k 0.00000 - 500.00000 - User original curve coefficient 0.00000OC2-a 0.00000 - 10.00000 - User original curve coefficient 0.00000OC2-c 0.00000 - 10.00000 - User original curve coefficient 0.00000OC2-kr 0.00000 - 500.00000 - User original curve coefficient 0.00000OC2-b 0.00000 - 10.00000 - User original curve coefficient 0.00000OC2-UseFor Trip / Alarm - OC2 out. selected for either Trip or alarm Trip(CH4 to CH23 are omitted)