6F2S1931 (0.20)Centralized GRB200(Soft: 030, 031, 032, 033, 034)- 612 -FUNFunction type (FUN) applied to a command response frame is set referring to Table 10.4-13.The FUN can be set to 0 to 255. When clicking the “Change all FUNs” on the Commonsetting screen, all FUNs are changed to the setting values at Common setting.DCO/Sig Off Name, Signal Off Desc., DCO Signal On Name, Signal On Desc.,Inverse“Sig off” and “Sig On” are used to set the Data ID of control object in General command.(Hereafter, these are described as “command output signal”.) “Inverse” is used to reversethe logic when controlling the command output signal.When the command output signal is treated as two signals (Sig Off Sig On), thecontrol scheme is shown as the following table by the combination of the receiving commandDCO and Inverse setting.For example, when the DCO=Off command is received under “Inverse” no-checked,the command output signal of “Sig Off” is controlled to “1”. “Sig On” is not controlled.Table 10.4-13 Control Scheme of Command Output Signal (Sig Off Sig On)“Inverse” checkedControl objectReceivingcommand DCOChecked No-checkedSignal specifiedto Sig.offSignal specifiedto Sig.onSignal specifiedto Sig.offSignal specified toSig.onOff Controlled to “1” Not controlled Controlled to “0” Not controlledOn Not controlled Controlled to “1” Not controlled Controlled to “0”When the command output signal is treated as one signal (Sig Off Sig On), thecontrol scheme is shown in Table 10.4-14. For example, when the DCO=On command isreceived under “Inverse” checked, the command output signals of “Sig On” and “Sig Off” arecontrolled to “0”. “Sig On” is not controlled.Table 10.4-14 Control Scheme of Command Output Signal (Sig Off = Sig On)“Inverse” checkedControl objectReceivingcommand DCOChecked No-checkedSignal specifiedto Sig.offSignal specifiedto Sig.onSignal specifiedto Sig.offSignal specifiedto Sig.onOff Controlled to “0” Controlled to ”1”On Controlled to ”1” Controlled to “0”When setting the “Sig Off”, “Sig On” and “Inverse”, check the specifications of thecommand output signals of communication and others, and then set them.Valid time