6F2S1931 (0.20)Centralized GRB200(Soft: 030, 031, 032, 033, 034)- 524 -(vii) IP setting example [RedundantMode]=Hot_standbyWhen Hot_standby is set for the setting [RedundantMode], the user can apply single IPaddress in the IED. The table shows that Port A and B have the same IP address.Table 10.2-4 Default IP address for Hot standby operationProtocol IEC61850(GOOSE) SNTP GR-TIEMS® /MULTIPLOG®IP address atPort A† 192.168.1.11 192.168.1.11 192.168.1.11IP address atPort B†IP addressfor Local PC Not applicable Not applicable 192.168.1.13‡†Note:Address ‘192.168.1.11’ is set as default. Setting [IPADDRESS2] will be neglected.‡Note: ‘192.168.1.13’ etc. can be set for the local engineering PC, if LAN for Local PC isready at C13.(viii) IP setting example [RedundantMode]=FixedIf Fixed is set for the setting [RedundantMode], the user can apply IP addresses in the IED.The table below shows that Port A, B, and C can have different IP addresses.Table 10.2-5 Default IP address for Fix operationProtocol IEC61850(GOOSE) SNTP GR-TIEMS® /MULTIPLOG®IP address atPort A† 192.168.1.11 192.168.1.11 192.168.1.11IP address atPort B Not applicable 192.168.1.12‡ 192.168.1.12§IP address atfor Local PC Not applicable Not applicable 192.168.1.13§†Note:Address ‘192.168.1.11’ is set as default.‡Note: An address can be set for SNTP, but it should not operate Time synchronizationwith Port A and Port B, which have different IP addresses.§Note: ‘192.168.1.13’ can be set for the local PC, if LAN for Local PC is ready at C13.