6F2S1931 (0.20)Centralized GRB200(Soft: 030, 031, 032, 033, 034)- 575 -Table 10.3-10 GOOSE statutes and signal outputsSignal values LCD screen messages GR-TIEMS screen messages0x0000 OK GOOD0xC000 NG QUESTIONABLE0xC010 NG QUESTIONABLE | TEST0xC040 NG QUESTIONABLE | INACCURATE0xC080 NG QUESTIONABLE | INCONSISTENTWhen the user wishes to see GOOSE outputs†, the user can see them by user’s PLC logic, butthe user should build its logic using the PLC function. Table 10.3-11 shows the GOOSE signals,which the user can select. For example, in order to get the GRL200_Bay1_4 information, theuser should take the GOOSE content using SUB_QUAL#3 output.Table 10.3-11 GOOSE output signalsData ID Signal names Descriptions301101 3100001001 SUB_QUAL#0 GOOSE subscription quality status301101 3100011001 SUB_QUAL#1 GOOSE subscription quality status301101 3100021001 SUB_QUAL#2 GOOSE subscription quality status301101 3100031001 SUB_QUAL#3 GOOSE subscription quality status301101 3100041001 SUB_QUAL#4 GOOSE subscription quality status~~~ ~~~ ~~~301101 31013E1001 SUB_QUAL#318 GOOSE subscription quality status301101 31013F1001 SUB_QUAL#319 GOOSE subscription quality status†Note: The user cannot view GOOSEs signal lists on the GR-TIMES engineering.10.3.9 Feature of IEC61850 Edition1 optionThe IED can have Private logical nodes, which are provided in Editon1_option, which aredesigned in Toshiba private specification exclusively. The user can select and add the followingData object:Table 10.3-12 LD class in Editon1 optionLD Class DO ContentGGIO AnInDatUpd DataUpdate Trigger is provided for general DataObject. The structure is the same as AnIn.Note: The option1 is designed to transfer the metering values during the fault on theIEC61850 Edition1.