6F2S1931 (0.20)Centralized GRB200(Soft: 030, 031, 032, 033, 034)- 227 -3.7.4 Operate logic for SBO/DIR modesAfter the operation of the select logic, the operate logic starts to clear the counters.(i) Receiving “Operate command Reset” from the remote-endFigure 3.7-10 depicts the reception of the operate command ‘Reset’ from the remote-end.Signal receptionin the IEC61850Operate command Reset from the remote-endDo nothingOperationdecisionSuccessFailedOperate logicWait for a commandSignal outputWait for a next commandSelect stageSelect commandReset from theremote-endSignal receptionfromthe front panelOperate command Reset from the local-endDo nothingOperationdecisionSuccessFailedOperate logic Signal outputFigure 3.7-10 Outline of Operate command ‘Reset’Mapping required for Input pointFigure 3.7-11 illustrates the operation logic when an “Operate command Reset (Remote-Reset-Control)” signal is applied to the GCNT01 function. The input-point “GCNT01_CMM_REQ” isused for the reception of the “Operate command Reset (Remote-Reset-Control)”.Output signal to BOThe GCNT01 function, in Figure 3.7-11, can provide a signal at the point “GCNT01_OK_CSC”,when the GCNT01 function determines that the signal “Remote-Reset-Control” is true.GCNT01 function (Function ID: 540001)Operate Cmd.GCNT01_CMM_REQCommand “Remote-Reset-Control”540001 700E016D09“GCNT01_EC_OK_CSC”(540001 820E011E84)& 1≥Input OutputOperate logic in GCNT01Statics-counterOperate condition‡Figure 3.7-11 Operate ‘On’ from the remote-end †††Note: To identify the input and output signal-points of the GCNT02–32 logics, see Table3.7-2 for the mapping points, Table 3.7-9 for the outputs.(ii) Receiving “Operate command Reset” from the local-endFigure 3.7-12 depicts the reception of the operate command ‘Reset’ from the local-end.