6F2S1931 (0.20)Centralized GRB200(Soft: 030, 031, 032, 033, 034)- 292 -4.4.6 Settings of binary input circuits(i) Setting table (IO_SLOT1) at MainUnit (IO#1) (Function ID: 200B01)Setting item Range Units Contents Default settingvalue NotesCommon THRES_Lvl Low / High - Determination of input threshold LowCMP_NUM 4 - 9 - Number of times filtered 4BI1 BI1_CPL Off / On - Programmable binary input enable OffOn Delay Timer 0.000 - 300.000 s On delay timer value 0.000Off Delay Timer 0.000 - 300.000 s Off delay timer value 0.000INVERSE-SW Normal / Inverse - Binary signal inversion NormalBI2 BI2_CPL Off / On - Programmable binary input enable OffOn Delay Timer 0.000 - 300.000 s On delay timer value 0.000Off Delay Timer 0.000 - 300.000 s Off delay timer value 0.000INVERSE-SW Normal / Inverse - Binary signal inversion Normal…… …… …… …… ……BI9 BI9_CPL Off / On - Programmable binary input enable OffOn Delay Timer 0.000 - 300.000 s On delay timer value 0.000Off Delay Timer 0.000 - 300.000 s Off delay timer value 0.000INVERSE-SW Normal / Inverse - Binary signal inversion Normal(ii) Setting tables (IO_SLOT2 to SLOT8) at MainUnit (IO#2 to IO#8)(Function ID: 200B02 to 200B08)Setting table is the same as the table for the IO#1.(iii) Setting tables (S1BIO_SLOT1 to 8) at SubUnit#1 (IO#1 to IO#8)(Function ID: 200B21 to 200B28)Setting table is the same as the table for the IO#1.(iv) Setting tables (S2BIO_SLOT1 to 8) at SubUnit#2 (IO#1 to IO#8)(Function ID: 200B31 to 200B38)Setting table is the same as the table for the IO#1.