2 Parameters2.2 List of parametersSINAMICS G130/G150676 List Manual (LH2), 04/2014, A5E03263479ADescription: Displays the actual status of the function generator.Value: 0: Inactive1: Generate accelerating ramp to offset2: Generate parameterized signal shape3: Generate braking ramp4: Function generator stopped due to missing enable signals5: Function generator waits for BI: p48196: Function generator parameterization has been checkedDependency: Refer to: p4800, p4819Description: Displays the status of the function generator.0 signal: Function generator inactive1 signal: Function generator runningDescription: Sets the operating mode of the function generator.Value: 0: Connection at connector output r48181: Connection at current setpoint after filter and r48182: Connection as disturbing torque and r48183: Connection at speed setpoint after filter and r48184: Connection at current setpoint before filter and r48185: Connection at speed setpoint before filter and r48186: Connection for free measurement function r4818 and r483499: Connection at physical address and r4818r4805 Function generator status / FG statusCU_G130_DP,CU_G130_PN,CU_G150_DP,CU_G150_PNCan be changed: - Calculated: - Access level: 3Data type: Integer16 Dyn. index: - Func. diagram: -P-Group: Trace and function generator Units group: - Unit selection: -Not for motor type: - Scaling: - Expert list: 0Min Max Factory setting0 6 -r4806.0 BO: Function generator status signal / FG status signalCU_G130_DP,CU_G130_PN,CU_G150_DP,CU_G150_PNCan be changed: - Calculated: - Access level: 3Data type: Unsigned32 Dyn. index: - Func. diagram: -P-Group: Trace and function generator Units group: - Unit selection: -Not for motor type: - Scaling: - Expert list: 0Min Max Factory setting- - -Bit field: Bit Signal name 1 signal 0 signal FP00 Bit 0 ON OFF -p4810 Function generator mode / FG operating modeCU_G130_DP,CU_G130_PN,CU_G150_DP,CU_G150_PNCan be changed: U, T Calculated: - Access level: 3Data type: Integer16 Dyn. index: - Func. diagram: -P-Group: Trace and function generator Units group: - Unit selection: -Not for motor type: - Scaling: - Expert list: 0Min Max Factory setting0 99 0