4 Faults and alarms4.2 List of faults and alarmsSINAMICS G130/G1501698 List Manual (LH2), 04/2014, A5E03263479AF33160 (N, A) Encoder 3: Analog sensor channel A failedMessage value: %1Message class: Position/speed actual value incorrect or not available (11)Drive object: VECTOR_GReaction: OFF1 (IASC/DCBRK, NONE)Acknowledge: PULSE INHIBITCause: The input voltage of the analog sensor is outside the permissible limits.Fault value (r0949, interpret decimal):1: Input voltage outside detectable measuring range.2: Input voltage outside the measuring range set in (p4673).3: The absolute value of the input voltage has exceeded the range limit (p4676).Remedy: For fault value = 1:- check the output voltage of the analog sensor.For fault value = 2:- check the voltage setting for each encoder period (p4673).For fault value = 3:- check the range limit setting and increase it if necessary (p4676).Reaction upon N: NONEAcknowl. upon N: NONEReaction upon A: NONEAcknowl. upon A: NONEF33161 (N, A) Encoder 3: Analog sensor channel B failedMessage value: %1Message class: Position/speed actual value incorrect or not available (11)Drive object: VECTOR_GReaction: OFF1 (IASC/DCBRK, NONE)Acknowledge: PULSE INHIBITCause: The input voltage of the analog sensor is outside the permissible limits.Fault value (r0949, interpret decimal):1: Input voltage outside detectable measuring range.2: Input voltage outside the measuring range set in (p4675).3: The absolute value of the input voltage has exceeded the range limit (p4676).Remedy: For fault value = 1:- check the output voltage of the analog sensor.For fault value = 2:- check the voltage setting for each encoder period (p4675).For fault value = 3:- check the range limit setting and increase it if necessary (p4676).Reaction upon N: NONEAcknowl. upon N: NONEReaction upon A: NONEAcknowl. upon A: NONEF33163 (N, A) Encoder 3: Analog sensor position value exceeds limit valueMessage value: %1Message class: Position/speed actual value incorrect or not available (11)Drive object: VECTOR_GReaction: OFF1 (IASC/DCBRK, NONE)Acknowledge: PULSE INHIBITCause: The position value has exceeded the permissible range of -0.5 ... +0.5.Fault value (r0949, interpret decimal):1: Position value from the LVDT sensor.2: Position value from the encoder characteristic.