SINAMICS G130/G150List Manual (LH2), 04/2014, A5E03263479A 2952 Parameters2.2 List of parametersNotice: The drive is enabled for jogging using BI: p1055 or BI: p1056.The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.Only the signal source that was used to power up can also be used to power down again.Description: Sets the signal source for jog 2.Recommend.: When the setting for this binector input is changed, the motor can only be switched on by means of an appropriatesignal change of the source.Dependency: Refer to: p0840, p1059Notice: The drive is enabled for jogging using BI: p1055 or BI: p1056.The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.Only the signal source that was used to power up can also be used to power down again.Description: Sets the speed for jog 1.Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.Dependency: Refer to: p1055, p1056Description: Sets the speed for jog 2.Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.Dependency: Refer to: p1055, p1056Description: Sets the speed limit/velocity limit effective in the setpoint channel.Dependency: Refer to: p1082, p1083, p1085, p1086, p1088p1056[0...n] BI: Jog bit 1 / Jog bit 1VECTOR_G Can be changed: T Calculated: - Access level: 3Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 2501, 3030P-Group: Setpoints Units group: - Unit selection: -Not for motor type: - Scaling: - Expert list: 1Min Max Factory setting- - 0p1058[0...n] Jog 1 speed setpoint / Jog 1 n_setVECTOR_G Can be changed: T Calculated: - Access level: 2Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3001, 3030P-Group: Setpoints Units group: 3_1 Unit selection: p0505Not for motor type: - Scaling: - Expert list: 1Min Max Factory setting-210000.000 [rpm] 210000.000 [rpm] 0.000 [rpm]p1059[0...n] Jog 2 speed setpoint / Jog 2 n_setVECTOR_G Can be changed: T Calculated: - Access level: 2Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3001, 3030P-Group: Setpoints Units group: 3_1 Unit selection: p0505Not for motor type: - Scaling: - Expert list: 1Min Max Factory setting-210000.000 [rpm] 210000.000 [rpm] 0.000 [rpm]p1063[0...n] Speed limit setpoint channel / n_limit setpVECTOR_G Can be changed: U, T Calculated: - Access level: 1Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3040P-Group: Setpoints Units group: 3_1 Unit selection: p0505Not for motor type: - Scaling: - Expert list: 1Min Max Factory setting0.000 [rpm] 210000.000 [rpm] 40000.000 [rpm]