2 Parameters2.2 List of parametersSINAMICS G130/G150114 List Manual (LH2), 04/2014, A5E03263479ADescription: Sets the run-up time of the cooling unit after a power-off command.Description: Displays the control word for the cooling unit.Description: Sets the signal sources for the feedback signals from the cooling unit.Index: [0] = Cooling unit powered up[1] = Cooling unit ready to be powered up[2] = Cooling unit no alarm present[3] = Cooling unit no fault present[4] = Cooling unit no leaked liquid[5] = Cooling unit liquid flow OK[6] = Cooling unit conductivity < fault threshold[7] = Cooling unit conductivity < alarm thresholdDescription: Displays the status word of the cooling unit.p0264 Cooling unit run-on time / RKA run-on timeB_INF (Cool_unit),VECTOR_G(Cool_unit)Can be changed: U, T Calculated: - Access level: 3Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9795P-Group: Converter Units group: - Unit selection: -Not for motor type: - Scaling: - Expert list: 1Min Max Factory setting0.0 [s] 180.0 [s] 30.0 [s]r0265.0...3 BO: Cooling unit control word / RKA STWB_INF (Cool_unit),VECTOR_G(Cool_unit)Can be changed: - Calculated: - Access level: 3Data type: Unsigned8 Dyn. index: - Func. diagram: -P-Group: Commands Units group: - Unit selection: -Not for motor type: - Scaling: - Expert list: 1Min Max Factory setting- - -Bit field: Bit Signal name 1 signal 0 signal FP00 Power up cooling unit Activating De-activating -01 Message converter off OFF ON -02 Acknowledge faults Acknowledgement No acknowledgement -03 Leakage sensing OK No leaked liquid Leaked liquid -p0266[0...7] BI: Cooling unit feedback signals signal source / RKA fdbk S_srcB_INF (Cool_unit),VECTOR_G(Cool_unit)Can be changed: U, T Calculated: - Access level: 3Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: -P-Group: Communications Units group: - Unit selection: -Not for motor type: - Scaling: - Expert list: 1Min Max Factory setting- - 1r0267.0...7 BO: Cooling unit status word / RKA ZSWB_INF (Cool_unit),VECTOR_G(Cool_unit)Can be changed: - Calculated: - Access level: 3Data type: Unsigned16 Dyn. index: - Func. diagram: -P-Group: Commands Units group: - Unit selection: -Not for motor type: - Scaling: - Expert list: 1Min Max Factory setting- - -Bit field: Bit Signal name 1 signal 0 signal FP00 RKA powered up Yes No -01 RKA ready to be powered up Yes No -02 RKA no alarm present Yes No -03 RKA no fault present Yes No -04 RKA no leaked fluid Yes No -