SINAMICS G130/G150List Manual (LH2), 04/2014, A5E03263479A 1012 Parameters2.2 List of parametersNote: The parameter is used to identify when the drive is being commissioned for the first time.The power unit commissioning can only be exited (p0201 = r0200), if the actual and acknowledged code numbers areidentical (p0010 = 2).For parallel circuit configurations, the parameter index is assigned to a power unit.Description: Sets the actual code number from r0200 to acknowledge the power unit being used.When commissioned for the first time, the code number is automatically transferred from r0200 into p0201.Notice: When p0201 = 10000, the rated power unit data is reloaded and dependent parameters are set (e.g. p0205, p0210,p0230, p0857, p1800). p0201 is then automatically assigned the value of r0200 if the code number of the power unitcould be read. A warm start must be performed after this procedure (automatically if necessary).Note: The parameter is used to identify when the drive is being commissioned for the first time.The power unit commissioning can only be exited (p0201 = r0200), if the actual and acknowledged code numbers areidentical (p0010 = 2). However, if the comparator in p9906 or p9908 is at 2 (low) or 3 (minimum), the power unitcommissioning is automatically set to p0201 = r0200 upon exiting.When the code number is changed, the connection voltage (p0210) is checked and, if necessary, adjusted.For parallel circuit configurations, the parameter index is assigned to a power unit.Description: Displays the type of power unit found.Value: 2: MICROMASTER 4403: MICROMASTER 4114: MICROMASTER 4105: MICROMASTER 4366: MICROMASTER 440 PX7: MICROMASTER 430100: SINAMICS S101: SINAMICS S (value)102: SINAMICS S (combi)103: SINAMICS S120M (distributed)112: PM220 (SINAMICS G120)113: PM230 (SINAMICS G120)114: PM240 (SINAMICS G120)115: PM250 (SINAMICS G120 / S120)116: PM260 (SINAMICS G120)118: SINAMICS G120 Px120: PM340 (SINAMICS S120)126: SINAMICS ET200PRO130: PM250D (SINAMICS G120D)133: SINAMICS G120C135: SINAMICS PMV40136: SINAMICS PMV60137: SINAMICS PMV80138: SINAMICS G110M150: SINAMICS G151: PM330 (SINAMICS G120)200: SINAMICS GMp0201[0...n] Power unit code number / PU code noVECTOR_G Can be changed: C2(2) Calculated: - Access level: 3Data type: Unsigned16 Dyn. index: PDS, p0120 Func. diagram: -P-Group: Converter Units group: - Unit selection: -Not for motor type: - Scaling: - Expert list: 1Min Max Factory setting0 65535 0r0203[0...n] Actual power unit type / PU actual typeB_INF, VECTOR_G Can be changed: - Calculated: - Access level: 3Data type: Integer16 Dyn. index: PDS, p0120 Func. diagram: -P-Group: Converter Units group: - Unit selection: -Not for motor type: - Scaling: - Expert list: 1Min Max Factory setting2 400 -