SINAMICS G130/G150List Manual (LH2), 04/2014, A5E03263479A 14314 Faults and alarms4.2 List of faults and alarmsPossible causes:- wire breakage or sensor not connected (KTY: R > 1630 Ohm).- measured resistance too low (PTC: R < 20 Ohm, KTY: R < 50 Ohm).Alarm value (r2124, interpret decimal):- if SME/TM120 is selected (p0601 = 10, 11),this is the number of the temperature channel leading to the message.Remedy: - make sure that the sensor is connected correctly.- check the parameterization (p0600, p0601).See also: r0035, p0600 (Motor temperature sensor for monitoring), p0601, p0607 (Temperature sensor fault timer)F07016 Drive: Motor temperature sensor faultMessage value: %1Message class: External measured value / signal state outside the permissible range (16)Drive object: VECTOR_GReaction: OFF1 (NONE, OFF2, OFF3, STOP2)Acknowledge: IMMEDIATELYCause: An error was detected when evaluating the temperature sensor set in p0600 and p0601.Possible causes:- wire breakage or sensor not connected (KTY: R > 1630 Ohm).- measured resistance too low (PTC: R < 20 Ohm, KTY: R < 50 Ohm).Note:If alarm A07015 is present, the time in p0607 is started. If the fault is still present after this time has expired, then faultF07016 is output; however, at the earliest, 50 ms after alarm A07015.Fault value (r0949, interpret decimal):- if SME/TM120 is selected (p0601 = 10, 11),this is the number of the temperature channel leading to the message.See also: p0607 (Temperature sensor fault timer)Remedy: - make sure that the sensor is connected correctly.- check the parameterization (p0600, p0601).- induction motors: De-activate temperature sensor fault (p0607 = 0).- When TM120 and SMC/SME (p0601 = 10, 11) are being used, set the same sensor type on the drive (p4610 ...p4613) as for TM120.See also: r0035, p0600 (Motor temperature sensor for monitoring), p0601, p0607 (Temperature sensor fault timer)F07080 Drive: Incorrect control parameterMessage value: Parameter: %1Message class: Error in the parameterization / configuration / commissioning procedure (18)Drive object: B_INF, ENC, HUB, TB30, TM150, TM31, TM54F_MA, TM54F_SL, VECTOR_GReaction: NONEAcknowledge: IMMEDIATELY (POWER ON)Cause: The closed-loop control parameters have been parameterized incorrectly (e.g. p0356 = L_spread = 0).Fault value (r0949, interpret decimal):The fault value includes the parameter number involved.The following parameter numbers only occur as fault values for vector drives:p0310, for synchronous motors: p0341, p0344, p0350, p0357The following parameter numbers do not occur as fault values for synchronous motors:p0354, p0358, p0360See also: p0310, p0311, p0341, p0344, p0350, p0354, p0356, p0357, p0358, p0360, p0400, p0404, p0408, p0640,p1082, p1300Remedy: Modify the parameter indicated in the fault value (r0949) (e.g. p0640 = current limit > 0).See also: p0311, p0341, p0344, p0350, p0354, p0356, p0358, p0360, p0400, p0404, p0408, p0640, p1082