E6581611E-35 Example of 4-20mA output adjustment (Refer to section 6.17.2 for details)=1, =0 =1, =20OutputcurrrentOutputcurrrentInternal calculated value Internal calculated value020(mA)0 100%420(mA)0 100%f692fmfmNote 1) When using the FM terminal for current output, be sure that the external load resistance is less than 600Ω.Use over 1kΩ external load resistance for voltage output.Note 2) = is the motor drive frequency. Adjusting the meter in inverter stop state Adjustment of the meter for output current (=1)Adjustment of the meter for output current can be done in inverter stop state.When setting to for fixed output 1 (output current 100% equivalent), a signal assuming thatinverter rated current (output current 100% equivalent) passes will be output from the FM terminal.Adjust the meter with the (Meter adjustment) parameter in this state.Similarly, if you set to for fixed output 2 (output current 50% equivalent), a signal assumingthat 50% of inverter rated current (output current 50% equivalent) passes will be output from the FMterminal.After meter adjustment is ended, set to (output current). Other adjustments ( = , to7, 9 to, , , , to ) = : When fixed output 3 (other than the output current) is set, a signal of the value for othermonitors is fixed at the following values and output through the FM terminal.100% standard value for each item is the following:=0, 2, 12, : Maximum frequency (h)=3, 4 : 1.5 times of rated voltage=7 : 2.5 times of rated torque=9 to11 : Rated load factor=13, , , : Maximum input value (10V, or 20mA)=18 : Maximum value (100.0%)=24, 25 : 1000x f749