E6581611M-613(Continued)Error code Problem Possible causes Remedies Output frequencyupper limit An attempt was made to operate at afrequency higher than 10 times the basefrequency ( or ). Operate at a frequency within 10 times thebase frequency. Operation panel keyalarm The RUN or STOP key is held down formore than 20 seconds. The RUN or STOP key is faulty. Check the operation panel. Control terminalblock connectionalarm Control terminal block comes off. Internal circuit is defective. Install the control terminal block to theinverter. Contact your Toshiba distributor. S3 terminal alarm Slide switch SW2 and parameter f147settings are different. Match the settings of SW2 and f147.Power supply OFF and ON after thesesettings. Auto-tuning Auto-tuning in process Normal if it the message disappears after afew seconds. Break in analogsignal cable The signal input via VIC is below theanalog signal detection level set with and setting value of isone or more. Check the cables for breaks. And check thesetting of input signal or setting value of and . In forced operation “” and operation frequency isdisplayed alternately in operation offorced fire-speed control. It is normal the alarm is gone out after theforced fire-speed control operation./Password verificationresult After the password setting (f738), thepassword was input to f739 (passwordverification). If the password is correct, pass is displayedand if it is incorrect, fail is displayed./Switching display ofEasy setting mode /Standard settingmode The EASY key was pushed in thestandard monitor mode. When easy is displayed, setting modebecomes easy setting mode. When std isdisplayed, it becomes standard setting mode.Note 2)Input requirement ofregion setting A region setting is not input yet. Power supplied to the inverter at first time As checking the region setting parameterset is set to 0, inverter return to defaultsetting. As typ is set to 13, inverter return todefault setting. Set a region setting by using setting dial.Refer to section 3.1. No trip of past trip No new record of past trip, after past tripswere clear. Normal operation. No detailedinformation of pasttrip The detailed information of past trip isread by pushing the center of setting dialduring blinking nerr ⇔ number. Normal operation.To be returned by pressing MODE key.[Prealarm display] Overcurrent alarm Same as (overcurrent) Overvoltage alarm Same as (overvoltage) Overload alarm Same as and (overload) Overheat alarm Same as (overheat) Communication alarm Same as err5 (communication fault)If two or more problems arise simultaneously, one of the following alarms appears and blinks., , The blinking alarms , , , h, t are displayed in this order from left to right.Note 2) is blinking after power supply is on. In this time, the keys are not operated.But parameter set is lighting as same as other parameters and is not blinking.