E6581611B-102TerminalsymbolInput /output Function Electricalspecifications Inverter internal circuitsOUTNO OutputMultifunction programmable opencollector output. Default setting detectand output speed reach signal.Multifunction output terminals to whichtwo different functions can be assigned.The NO terminal is an equipotentialterminal. It is isolated from the CCterminal.By changing parameter f669 settings,these terminals can also be used asmultifunction programmable pulse trainoutput terminals.Open collectoroutput24Vdc-100mATo output pulsetrains,a current of 10mAor more needs tobe passed.Pulse frequencyrange:10~2kppsFLAFLBFLCNote 3)OutputMultifunction programmable relay contactoutput.Detects the operation of the inverter'sprotection function. (Default setting)Contact across FLA-FLC is closed andFLB-FLC is opened during protectionfunction operation.Max. switchingcapacity250Vac-2A30Vdc-2A(cos=1): at resistive load250Vac-1A(cos=0.4)30Vdc-1A(L/R=7ms)Min. permissibleload5Vdc-100mA24Vdc-5mARYRCNote 3)OutputMultifunction programmable relay contactoutput.Default settings detect and output low-speed signal output frequencies.Multifunction output terminals to whichtwo different functions can be assigned.Max. switchingcapacity250Vac-2A(cos=1): at resistive load30Vdc-1A250Vac-1A(cos=0.4)Min. permissibleload5Vdc-100mA24Vdc-5mANote 1) When VIA terminal is used as logic input terminal, be sure to connect a resistor between P24 and VIA in case of sinklogic, between VIA and CC in case of source logic. (Recommended resistance: 4.7kΩ-1/2W)It is not needed for VIB terminal.Note 2) 100mA is the sum of P24 and +24.Note 3) A chattering (momentary ON/OFF of contact) is generated by external factors of the vibration and the impact, etc. Inparticular, please set the filter of 10ms or more, or timer for measures when connecting it directly with input unit terminalof programmable controller. Please use the OUT terminal as much as possible when the programmable controller isconnected.4.7NOPTCOUT4.7+24VRYRC+24VFLBFLAFLC