E6581611M-413(Continued)Error code Failure code Problem Possible causes Remedies The motor parameter , , ,, are not set correctly. Set the left column parameters correctlyas a motor name plate and make an auto-tuning again. Set parameter f416 to smaller 70% ofthe present value, and execute the auto-tuning again. The motor with the capacity of 2 classesor less than the inverter is used. The output cable is too thin. The inverter is used for loads other thanthose of three-phase induction motors. Set the left column parameters correctlyas a motor name plate and make an auto-tuning again. Then set f400=1, when trip occurs. The motor is not connected. Connect the motor. Check whether the secondary magneticcontactor. The motor is rotating. Make an auto-tuning again after therotation of the motor stops.0028005400550056Auto-tuning error Parameter pt=6 is set and High speedmotor is connected. Choose the higher power range drive.(1 class up drive is recommended.) A ground fault occurs in the output cableor the motor. Check the cable and the motor for groundfaults. Overcurrent of dynamic braking resistor Increase the deceleration time dec. Set the supply voltage correction f307to 1 or 3. 0022 Ground fault When inverters are fed by AC powersupply and connected with common DCbus link, unnecessary trip occurs. Set the parameter f614 to 0“Disabled”.*002F Step-out (for PMmotor drive only) The motor shaft is locked. One output phase is open. An impact load is applied. Using the DC braking function. Unlock the motor shaft. Check the interconnect cables betweenthe inverter and the motor. Prolong the acceleration / decelerationtime. Turn off the Step-out function when usingthe DC braking function or change the DCbraking to Servo lock function. 0029 Inverter type error It may be a breakdown failure. Contact your Toshiba distributor. 002D Over speed fault The input voltage fluctuates abnormally. Over speed fault due to the overvoltagelimit operation. Check the input voltage. Install an optional dynamic brakingresistor. (optional)*0032 Analog input breakdetection fault The input signal from VIC is equal to orless than the setting. Check the VIC signal cable for breaks.Also, check the input signal value orsetting of . 0033 CPU communicationserror A communications error occurs betweencontrol CPUs. Contact your Toshiba distributor. 0034 Over torque boostfault The automatic torque boost parameter setting is too high. The motor has too small impedance. Set a lower automatic torque boostparameter setting. Make an auto-tuning. 0035 CPU fault 2 The control CPU is defective. Contact your Toshiba distributor. 0037 Optional unit fault 2 An optional device is defective. Contact your Toshiba distributor. 003A CPU fault 3 The control CPU is defective. Contact your Toshiba distributor. 0057 Internal circuit fault Internal circuit is defective. Contact your Toshiba distributor. 0040 PTC fault PTC thermal protection is occurred. Check the PTC in motor. 0045 Servo lock fault The motor shaft is not locked in servo lockoperation. Reduce the load in servo lock operation.* This marking trips can be selected valid or invalid by parameters.(Continued overleaf)