E6581611F-11966.32 Analog input terminal function selectionf214 : VIB input point 1 ratef215 : VIB input point 2 ratef663 : Analog input terminal function selection (VIB)• FunctionParameter is normally set from operation panel. However some parameters can be continuously set fromexternal analog input by using this function. VIB terminal is used.[Parameter setting]Title Function Adjustment range Default settingf214 VIB input point 1 rate -250-+250 (%) 0f215 VIB input point 2 rate -250-+250 (%) 100f663 Analog input terminal functionselection (VIB)0: Frequency command1: Acceleration/deceleration time2: Upper limit frequency3, 4: -5: Torque boost value6: Stall prevention level7: Motor electronic-thermal protection level8 to 10: -11: Base frequency0+ Analog input terminal function assigns VIB terminal. The range of analog input voltage is 0% to +100%.From -100% to 0% cannot be used.+ The parameter that is selected by f663 can be adjusted range as following table.Setting of f663 Object parameter VIB : 0% input VIB : 100% input0: Frequencycommand - - -1: Acceleration/deceleration timeacc, dec, f500,f501, f510, f511Parameter setting value xf214Parameter setting value xf2152: Upper limitfrequency ul Parameter setting value xf214Parameter setting value xf2155: Torque boostvalue vb, f172 Parameter setting value xf214Parameter setting value xf2156: Stall preventionlevel f185, f601 Parameter setting value xf214Parameter setting value xf2157: Motor electronic-thermal protectionlevelthr, f173 Parameter setting value xf214Parameter setting value xf21511: Base frequency vlv, f171 Parameter setting value xf214Parameter setting value xf215Note: Adjustments are made by the inverter itself, so no changes are made to parameter settings