E6581611G-1377.3.1 Settings depending on voltage (0 to 10 V) inputYou can set the frequency settings by connecting the external potentiometer (1k to 10kΩ) between PP, VIA, andCC terminals.You can also set by inputting an analog voltage signal of 0 to 10Vdc between the VIA and CC terminals.The following shows examples when the run command is input from the terminal.Title Function Adjustment range Default setting Setting example Command mode selection 0 - 4 1(panel keypad)0(terminal block) Frequency setting modeselection 1 0 - 14 0(setting dial 1)1(terminal VIA) Analog/logic input selection(VIA/VIB) 0 - 4 0 0 or 1(Analog input) VIA input point 1 setting 0 - 100% 0 0 VIA input point 1 frequency 0.0 - 500.0Hz 0.0 0.0 VIA input point 2 setting 0 - 100% 100 100 VIA input point 2 frequency 0.0 - 500.0Hz *1 50.0/60.0 Analog input filter 2 - 1000 ms 64 64*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.MotorMR/L1 U/T1MCCBPowerSupply S/L2T/L3V/T2W/T3CCFRRESFLCS1S2VF-S15 Run and stop settingsYou can switch between forward run (F)and reverser run (R), and run/stop withexternal signals. Setting characteristics for the voltageinput signal and frequencySet characteristics at two points.ForwardrunReverserunS3* Connect a single-phaseinput model to R/L1 andS/L2/N. FLAFLBHz% Point 2Point 1Voltage input signal0% 100%(0V) (10 V)FrequencyCC VIA PP