E6581611J-11010. Peripheral devicesWarningMandatoryaction When using switchgear for the inverter, it must be installed in a cabinet.Failure to do so can lead to risk of electric shock.Be Grounded Ground must be connected securely.If the ground is not securely connected, it could lead to electric shock or fire.10.1 Selection of wiring materials and devices Selection of wire sizeWire size (mm²) Note 4)Power circuit Note 1) Note 5)Input Output DC Reactor (Optional)without DCL with DCLVoltageclassApplicablemotor(kW)IECCompliantFor Japan*1IECCompliantFor Japan*1IECCompliantFor Japan*1IECCompliantFor Japan*10.4 1.5 2.0 1.5 2.0 1.5 2.0 1.5 2.00.75 1.5 2.0 1.5 2.0 1.5 2.0 1.5 2.01.5 1.5 2.0 1.5 2.0 1.5 2.0 1.5 2.02.2 2.5 2.0 1.5 2.0 1.5 2.0 1.5 2.04.0 4.0 2.0 2.5 2.0 2.5 2.0 4.0 2.05.5 10 5.5 4.0 2.0 6.0 3.5 6.0 3.57.5 16 8.0 6.0 3.5 10 3.5 10 5.511 25 14 10 5.5 16 8.0 16 8.015 35 22 16 14 25 14 25 143 phase240Vclass18.5 50 22 25 14 35 14 35 220.2 1.5 2.0 1.5 2.0 1.5 2.0 1.5 2.00.4 1.5 2.0 1.5 2.0 1.5 2.0 1.5 2.00.75 1.5 2.0 1.5 2.0 1.5 2.0 1.5 2.01.5 2.5 2.0 2.5 2.0 1.5 2.0 2.5 2.02.2 4.0 2.0 4.0 2.0 1.5 2.0 4.0 2.01 phase240Vclass3.0 4.0 2.0 4.0 2.0 1.5 2.0 4.0 2.00.4 1.5 2.0 1.5 2.0 1.5 2.0 1.5 2.00.75 1.5 2.0 1.5 2.0 1.5 2.0 1.5 2.01.5 1.5 2.0 1.5 2.0 1.5 2.0 1.5 2.02.2 1.5 2.0 1.5 2.0 1.5 2.0 1.5 2.04.0 2.5 2.0 1.5 2.0 1.5 2.0 1.5 2.05.5 4.0 2.0 1.5 2.0 2.5 2.0 2.5 2.07.5 6.0 3.5 2.5 2.0 2.5 2.0 4.0 2.011 10 5.5 4.0 2.0 6.0 3.5 6.0 3.515 16 8.0 6.0 3.5 10 3.5 10 5.53 phase500Vclass18.5 16 8.0 10 5.5 10 5.5 16 8.0