E6581611E-1955.8 Switching between two frequency commandsfmod : Frequency setting mode selection1f200 : Frequency priority selectionf207 : Frequency setting mode selection2 FunctionThese parameters are used to switch between two frequency commands automatically or with inputterminal signals.Parameter settingTitle Function Adjustment range Default settingfmod Frequency setting modeselection 1 0f207 Frequency setting modeselection 20: Setting dial 1(save even if power is off)1: Terminal VIA2: Terminal VIB3: Setting dial 2(press in center to save)4: RS485 communication5: UP/DOWN from external logic input6: CANopen communication7: Communication option8: Terminal VIC9, 10: -11: Pulse train input12, 13: -14: sro1f200 Frequency priority selection0: fmod (Switchable to f207by terminal input)1: fmod (Switchable to f207 at 1.0 Hzor less of designated frequency)01) Switching with input terminal signals (Input terminal function 104/105: FCHG)Frequency priority selection parameter f200 = 0Switch frequency command set with fmod and f207 by the input terminal signals.Assign frequency setting mode forced switching function (input terminal function selection: 104) to aninput terminal.If an OFF command is entered to the input terminal block: The frequency command set with fmod.If an ON command is entered to the input terminal block: The frequency command set with f207.Note) Input terminal function 105 is the inverse signal of the above.